AC VOLTAGE INDICATOR / MONITOR / WINDOW COMPARATOR OVER / UNDER CURRENT PROTECTION
0 RELAY
This device is used to display DC voltage.
Maximum & Minimum values are logged for 24 hours (updated every 60 min).
Use the “ScAL” parameter for calibration purposes, or to change the number of decimal places displayed (see notes).
Other features include adjust able signal damping & all settings may be locked & code protected to avoid changes from being made by unauthorised personnel.
ADDITIONAL FEATURES INCLUDE:
ADJUSTABLE PARAMETERS:
SCALE : 1A - 9999A
DECIMAL POINTER : 0.000 / 0.00 / 0.0 / 0
UPPER LIMIT : 1A - full scale
LOWER LIMIT : 1A - full scale
HYSTERESIS: 1A - full scale
START-UP DELAY: 0 - 99 seconds
REACTION DELAY (TRIPP DELAY): 0 - 99 seconds
CALIBRATION: 90% - 110%
RESPONSE TIME :<1-4 sec
Specifications:
Accuracy: 1% of full scale (sinusoidal inputs) Typically 0.5% at 25 °C.
Scale: 5 to 5000
Peak instantaneous current: 5A device: 8A
Full wave: 8/e2=5.65A RMS.
Half wave: 8A/2=4A RMS
1A device: 1.6A
Full wave: 1.6A/e2=1.13 A RMS.
Half wave: 1.6A / 2=0.8A RMS)
Input voltage: ±15% of rated voltage
Led indication: Relay status
Response time: <1.1 sec
Start-up delay: 1 to 100 sec (0.5 sec intervals)
Reaction delay: 0 to 100 sec (0.5 sec intervals)