AC VOLTAGE INDICATOR / MONITOR / WINDOW COMPARATOR OVER / UNDER CURRENT PROTECTION
2 RELAY
This device provides OVER and / or UNDER current protection. The display may be scaled to any value from 5 to 5000 and the decimal pointer set to any position. This allows the device to be configured for any primary CT current with up to 3 decimal places. Each relay is controlled via separate upper, lower and hysteresis set-points. The relays may therefore be configured for both over and / or under, or one for over and the other for under current protection. Programmable ‘start-up’ and ‘reaction’ delays are included.
ADDITIONAL FEATURES INCLUDE:
ADJUSTABLE PARAMETERS:
SCALE : 1A - 9999A
DECIMAL POINTER : 0.000 / 0.00 / 0.0 / 0
UPPER LIMIT : 1A - full scale
LOWER LIMIT : 1A - full scale
HYSTERESIS: 1A - full scale
START-UP DELAY: 0 - 99 seconds
REACTION DELAY (TRIPP DELAY): 0 - 99 seconds
CALIBRATION: 90% - 110%
RESPONSE TIME :<1-4 sec
ACCURACY:
0.25%
Specifications:
Accuracy: 1% of full scale (sinusoidal inputs) Typically 0.5% at 25 °C.
Scale: 5 to 5000
Peak instantaneous current: 5A device: 8A
Full wave: 8/e2=5.65A RMS.
Half wave: 8A/2=4A RMS
1A device: 1.6A
Full wave: 1.6A/e2=1.13 A RMS.
Half wave: 1.6A / 2=0.8A RMS)
Input voltage: ±15% of rated voltage
Led indication: Relay status
Response time: <1.1 sec
Start-up delay: 1 to 100 sec (0.5 sec intervals)
Reaction delay: 0 to 100 sec (0.5 sec intervals)