Pre select counter/ high frequency monitor dislay and count a pre-set number of pulses dislay and monitor frequencies up to 10000Hz
0 RELAY
This device may be configured for counting or frequency monitoring functions.
Using the "save" function, the state of the counter is saved to non-volatile memory during power failures. This allows the device to continue from where it left off before the power was removed.
A 10V - 24V DC supply (± 30mA) is included for use with NPN proximity switches.
Pulses can be acknowledged when the pulse pins are either shorted OR released.
A pre-scaler of up to 200 is included. (the device reads the "pre scale" amount of pulses before updating the counter value).
The post-scaler multiplies the pulses received by up to 200.
Pulses may be displayed as lapsed (up-counting), remaining (down counting) or frequency (even if configured for counting).
Using the reset timer the device can automatically be reset between 0.1 and 99.9 seconds after the pre-set number of pulses have been counted. This eliminates the need to generate reset pulses manually.
ADDITIONAL FEATURES INCLUDE:
ADJUSTABLE PARAMETERS:
FUNCTION: counter/frequency
SET POINT: 1-49999 pulses
RELAY OUTPUT: continous/pulse
REVERSE RELAY (relay status after counting): open/close
PRE-SCALE (pulses/count): 1-200 pulses
POST-SCALE (count/pulses): 1-200
INPUT PULSE SPEED: mechanical/fast
PULSE EDGE (leading/trailing): close/open
KEYPAD AND MENU LOCK
Specifications:
Input range: 0-9999 pulses,0-9999 RPM,0-5000Hz, 0-9999 pulses per hour
Maximum display value: 9999
Pre-scale: 1-1000 pulses
Post-scale: 1-1000
Decimal pointer: 9999, 9.999, 99.99, 999,9
Accuracy: Counter mode : 100%
Freq, RPM,PPh : ±0.05%
Display Resolution: Counter: 0.001 to 9999
Freq, RPM, PPh: 1
Input voltage: ±15% of rated voltage
Led indication: Relay status
Reset time: 0.5 sec (power supply reset) 0.05 sec (reset pulse)
Response time: Counter: <0.02s
Freq, RPM, PPh: <1.1s
Input frequency “FASt”: 0-8000 Hz “SLO”: 0-5 Hz
Pulse source type mechanical switch or NPN proximity
All parameters are saved to non-volatile eeprom memory, thus eliminating the need to re-program after a power failure
incorporates a crystal oscillator to maintain accurate timing