DC VOLTAGE INDICATOR / MONITOR / WINDOW COMPARATOR OVER / UNDER VOLTAGE PROTECTION
Standard device reads voltages from 0V - 150V DC (other ranges on request)
0 RELAY
This device is used to display DC voltage.
Maximum & Minimum values are logged for 24 hours (updated every 60 min).
Use the “ScAL” parameter for calibration purposes, or to change the number of decimal places displayed (see notes).
Other features include adjust able signal damping & all settings may be locked & code protected to avoid changes from being made by unauthorised personnel.
ADDITIONAL FEATURES INCLUDE:
ADJUSTABLE PARAMETERS:
SCALE : 1V - 9999V
DECIMAL POINTER : 0.000 / 0.00 / 0.0 / 0
UPPER LIMIT : 1V - full scale
LOWER LIMIT : 1V - full scale
HYSTERESIS: 1V - full scale
START-UP DELAY: 0 - 99 seconds
REACTION DELAY (TRIPP DELAY): 0 - 99 seconds
CALIBRATION: 90% - 110%
RESPONSE TIME :<1-4 sec
ACCURACY:
0.25%
CONTACT RATING:
10A 250V AC
TECHNICAL INFORMATION:
LED INDICATION:
relay status, Volts