rue RMS THREE PHASE VOLTAGE INDICATOR / MONITOR / WINDOW COMPARATOR OVER / UNDER VOLTAGE & FREQUENCY (VM32) MONITOR


R1868.10 

Learn More


1 RELAY

In addition to providing OVER and / or UNDER voltage protection, this device will monitor phase failure, phase reversal and phase imbalance (neutral failure on “N” devices).
It incorporates upper and lower voltage set-points, a programmable start-up delay, trigger delay, recovery delay, hysteresis, phase imbalance limit and phase imbalance hysteresis.
By changing the calibration setting, the readings may be adjusted from 90 to 110%.
The individual phase-to-phase voltages are monitored and can be viewed by pressing the “+” button.
Every key-press cycles the display in the following order: the voltage between phase 1 and 2, then 1 and 3, then 2 and 3, line frequency and the average of all three phases.
Under normal conditions the average of all 3 phases is displayed.
Under fault conditions, the display indicates the offending phases using the left hand character, and the message “Hi” or “Lo”.
A phase imbalance or reversal is indicated by “PH.ib” or “Ph.Er”. If the start-up or trigger delay holds the relay energised during a fault condition, the display indicates “-r1-“ as a warning.
The same message is displayed when the relay is held in the de-energised state by the recovery delay. A latch facility is also incorporated.

ADDITIONAL PROTECTION AGAINST:

  • over / under voltage
  • over / under frequency (VM32 only)
  • loss of neutral (VM3x-N only)
  • phase imbalance (phase to phase voltages)
  • phase failure
  • phase reversal
  • phase angle error
  • regenerated EMF

 

ADDITIONAL FEATURES INCLUDE:

  • adjustable START-UP DELAY
  • REACTION DELAY
  • RECOVERY DELAY
  • LATCH FACILITY to force mechanical reset after fault
  • monitors own supply and frequency
  • keypad lock with code

 

ADJUSTABLE PARAMETERS:

UPPER LIMIT : 150V - 500V

LOWER LIMIT : 150V - 500V

HYSTERESIS: 1V - 20V

PHASE IMBALANCE: 0V - 20V

PHASE IMBALANCE HYSTERESIS: 0V - 20V

FREQUENCY: 45Hz - 55Hz

START-UP DELAY: 0 - 99 seconds

REACTION DELAY (TRIPP DELAY): 0 - 99 seconds

RECOVERY DELAY (min relay off time: 0 - 99 seconds

ACCURACY:

 0.3% of full scale

CONTACT RATING:

 10A 250V AC

TECHNICAL INFORMATION:

  • TRUE RMS by taking ± 150 readings per cycle
  • all parameters are saved to non-volatile EEPROM memory, eliminating the need to re-program after power failure


LED INDICATION:

 relay status, ave of 3 phases, phase to phase V, frequency

Download User Manual Here